DescriptionFeaturesSpecification parameterDetailed description
It is applied to the reactive power compensation system. The reactor is used in series with the capacitor to compensate the reactive power in the power grid and improve the power factor. The reactor and the shunt capacitor tuning can filter the specific frequency harmonics, and the reactor has the function of suppressing the closing inrush and protecting the capacitance.
The transformer selects the high quality silicon steel sheet and the advanced vacuum lacquer and the European production technology. The product has the power of energy saving, low loss, low noise, shock resistance and short circuit resistance. The advantages of strong overload capacity, compact structure, small size, convenient installation, etc.
System
voltage
|
220V-690V
|
Rated
current
|
5A-500A
|
Inductance
|
20uH-10mH
|
Inductance
deviation
|
±10%
|
Working
frequency
|
50Hz/60Hz
|
Reactance ratio
|
3%-14%
|
Number
of phase
|
1
phase / 3 phases.
|
Insulation
class
|
F(155℃)/H(180℃)/R(220℃)
|
Type
of cooling
|
AN/AF
|
Noise
|
≤65dBA
|
Efficiency
|
>98%
|
Reference standard :
GB1094.1,
GB1094.6, GB1094.11, JB9644, IEC60076
Use of the environment :
|
|
Working environment Temperature
|
-25℃-55℃
|
Sea height
|
≤2000m,Exceed the drop in use
|
Relative humidity
|
<90%
|